HFO purifier loses its water seal after changing to VLSFO. What should be checked?

Ask a question
Asked 5 d ago · 1 answer
Vote

After changing to VLSFO, an HFO purifier loses the water seal every few hours and the sludge discharge alarm goes off. The bowl is clean and the gravity disc was changed using the density chart. Operating water pressure is normal. What else should be checked?

TankerBulk
asked 5 d agoAdmin

1 answer

Vote

With VLSFO the usual cause is still the gravity disc, because density changes a lot between bunkers.

  • Use the density from the latest bunker report, not an older one.
  • Keep the separation temperature stable (typically 98 ?C, per the maker's manual). A slow heater control can break the seal.
  • Check the sealing water and displacement water timer settings. Many ships still have the HFO values.
  • Check the water seal solenoid valve. One that sticks only when warm gives the same alarm pattern.

If all of that is right, open the purifier and check the bowl hood seal ring for hardening or cracks.