Intermittent PT100 "sensor fail" alarm on an exhaust temperature. Where to start?

Ask a question
Asked 4 d ago · 1 answer
Vote

A PT100 exhaust temperature alarm comes and goes, mostly in rough weather. Resistance at the sensor reads correct when cold and the wiring looks fine at the junction box. Where to start?

Container
asked 4 d agoAdmin

1 answer

Vote

Intermittent faults in rough weather usually mean a loose connection, a damaged conductor or moisture, not a bad sensor.

  • Check terminal tightness at the sensor head and in the junction box. Vibration loosens them.
  • PT100s are often wired with 3 wires. A loose compensation wire gives exactly this kind of fault.
  • Look for oil or water in the cable gland and junction box.
  • With the sensor disconnected, test the cable's insulation to earth.
  • Check the cable where it flexes near the gland. A cracked conductor can open only when the engine moves.

If all is fine, swap the sensor with a neighbouring cylinder and see whether the fault moves.